Hichai 200-600KW Diesel Generator Set | Top China Suppliers & Factory for PERKINS Series Generators
CCEC Generator Sets Specification
| Genset Model | Standby Power | Prime Power | Engine Model | Dimension (mm) | Weight (KG) | ||
|---|---|---|---|---|---|---|---|
| KVA | KW | kVA | KW | ||||
| KH-200GF | 275 | 220 | 250 | 200 | NT855-GA | 2980*1000*1700 | 2320 |
| 275 | 220 | MTA11-G2A | 2980*1000*1700 | 2320 | |||
| KH-250GF | 330 | 264 | 312.5 | 250 | NTA855-G1A | 2980*1000*1700 | 2450 |
| 358 | 286 | MTAA11-G3 | 3150*1050*1700 | 2450 | |||
| KH-275GF | 385 | 308 | 343.7 | 275 | NTA855-G2A | 3100*1000*1700 | 2600 |
| KH-300GF | 418 | 334 | 375 | 300 | NTAA855-G7 | 3400*1280*1800 | 3050 |
| KH-320GF | 462 | 370 | 400 | 320 | NTAA855-G7A | 3400*1280*1800 | 3050 |
| KH-360GF | 495 | 396 | 450 | 360 | KTA19-G3 | 3300*1350*2000 | 3600 |
| KH-400GF | 550 | 440 | 500 | 400 | KTA19-G3A | 3420*1250*1930 | 3720 |
| KH-420GF | 605 | 484 | 525 | 420 | KTAA19-G5 | 3550*1550*2100 | 4000 |
| KH-500GF | 688 | 550 | 625 | 500 | KTA19-G6A | 3550*1550*2100 | 4400 |
| KH-600GF | 858 | 686 | 750 | 600 | KTA38-G2 | 4260*1650*2350 | 6350 |
DCEC Generator Sets Specification
| Genset Model | Standby Power | Prime Power | Engine Model | Dimension (mm) | Weight (KG) | ||
|---|---|---|---|---|---|---|---|
| KVA | KW | KVA | KW | ||||
| KH-350GF | 495 | 396 | 437.5 | 350 | QSZ13-G2 | 3150*1360*1870 | 2600 |
| KH-400GF | 550 | 440 | 500 | 400 | QSZ13-G3 | 3150*1360*1870 | 2670 |
Component Details
Frequently Asked Questions (FAQ)
What is the difference between Standby Power and Prime Power?
Standby Power is the maximum power available for emergency use during utility outages under varying load factors. Prime Power is the continuous power rating designed for unlimited run hours in utility-free operations, typically with a 10% overload capacity allowed for short durations.
Which engine models are used in CCEC generator sets?
CCEC generator sets utilize high-performance Cummins engines, including the NT855, MTA11, NTA855, NTAA855, KTA19, KTAA19, and KTA38 series, covering a wide range of power outputs from 200KW to 600KW.
What engines power the DCEC generator sets listed?
The DCEC generator sets listed (KH-350GF and KH-400GF) are powered by Cummins QSZ13 series engines, specifically the QSZ13-G2 and QSZ13-G3 models, offering reliable performance for mid-to-high power requirements.
How do I determine the appropriate generator set size?
You should calculate your total power load requirement in kilowatts (KW) or kilovolt-amperes (KVA), factoring in start-up currents for heavy machinery. Compare your requirements against the Prime and Standby Power ratings listed in our specification tables.
Are the dimensions and weights of the generator sets fixed?
The dimensions (mm) and weights (KG) provided in the tables are standard configurations for open-type generator sets. Optional accessories, such as soundproof canopies or mobile trailers, will alter the final dimensions and weights.

By Engine
Cummins
Baudouin
By Power
68KW
By Function
Silent Genset